SECTION 12490 INTERIOR ROLLER SHADES

PART 1. GENERAL
1.01 SUMMARY

A. SCOPE
  1. The following specifications detail the minimum performance and related criteria for an electronic shade control system used on this project
  2. This specification covers electronic shading systems, controls, and materials as specified in locations indicated on architectural plans
1.02 RELATED SECTIONS AND DOCUMENTS
A. RELATED DOCUMENTS
  1. Drawings and General provisions of the Contract, including General and Supplementary Conditions apply to this section
A. RELATED SECTIONS
  1. Section 09250 - Substrate for window shade systems and installation of shade pockets, pocket closure, and/ or accessories supplied only under this section.
  2. Section 16000 - Electrical; installation of and connections to electrical motor control system and lighting control system components supplied only by this section as required to accomplish control requirements specified elsewhere and as indicated in the drawings.
1.03 RESPONSIBILITY FOR WINDOW TREATMENT SYSTEM

A. The responsibility for the design, engineering, installation, and performance of motorized window shade systems specified in this section shall be assigned to a single manufacturer and their authorized dealers/installers.

B. The Base Building Contractor (Main Contractor) shall coordinate installation of the following items with the Window Shade contractor for all window treatment systems:

a. Metal shade pockets recessed into ceiling system and ceiling trim (closure flap) or assembly.

C. The Base Building Contractor (Main Contractor) shall provide the following materials and services to the window shade contractor for electrically powered window treatments:

a. Power wiring in accordance with requirements provided by the Window Shade Contractor.

b. Low-voltage wiring as necessary for operation of shade control system. (Window Shade Contractor shall specify power needs to General Contractor)

1.04 SUBMITTALS
A. PRODUCT DATA
  1. Submit manufacturer’s descriptive literature for each product type specified. Details shall indicate materials, finishes, construction, and mounting requirements. Also include installation, wiring, and operating instructions.
B. SHOP DRAWINGS
  1. Indicate Head, jamb, and sill details to aid Base Building contractor to coordinate work as well as relevant dimensions and mounting requirements for each product type and mounting condition.
  2. System one-line wiring diagrams including connection details and overall arrangement of all shades and control locations supplied by this section for installation and connection by division 16.
C. SAMPLES
  1. Selection Samples:

a. Portfolio of shade fabric swatches for initial fabric color selection from manufacturer’s full range of available fabrics.

b. Material samples for color and finish selection of controls.

1.05 QUALITY ASSURANCE
A. QUALIFICATIONS
  1. Manufacturer shall have 15 years minimum experience manufacturing products comparable to those specified in this section. The manufacturer, subsidiary, or licensed agent shall be approved to supply the products specified and to honor any claims against the product presented in accordance with the warranty.
1.06 DELIVERY, STORAGE, AND HANDLING
A. STORAGE AND PROTECTION
  1. Deliver shades to project in protective packaging, uniquely labeled to identify each shade for each opening. Schedule delivery to prevent delays to completion of work, but to minimize on-site storage time.
E. SCHEDULING
  1. Coordinate construction of surrounding conditions to allow for timely field dimension verification.
  2. Manufacturer’s standard lead times apply. Reference submittal and schedule accordingly for project timeline.
PART 2. PRODUCTS
2.01 MANUFACTURERS

A. To establish the standard of quality, design, and function desired, drawings and specifications are based on products by:

DFB Sales Inc.
21-07 Borden Ave.
Long Island City, NY 11101
Phone: 718 - 729-8310
Fax: 718 - 706-0526
E-mail: Sales@dfbsales.com
Web Site: www.dfbsales.com

B. All proposed alternates (clearly delineated as such) must be submitted in writing for approval by the Design Professional a minimum of 10 days prior to bid date and must be made available to all bidders. Proposed alternatives must be accompanied by a review of the specification noting compliance or noncompliance on a line-by-line basis. See section 01630 for instructions regarding submittal requirements for alternate or substitute products.

2.02 GENERAL SYSTEM SPECIFICATIONS A. OPERATION
  1. The Electronic Drive Unit shall operate without exceeding a 44dBA Sound Pressure Level (SPL) measured three (3) feet from the motor.
  2. The system shall make no audible clicks when the motor starts or stops.
  3. For systems with multiple Electronic Drive Units, Drive Units are electronically synchronized and will start, stop and move smoothly in unison at all times.
  4. System groups and subgroups can be reconfigured at the point of control without rewiring or access to the Electronic Drive Unit
  5. The Electronic Drive Unit shall be powered via a UL Listed or UL Recognized Class 2 Power Supply.
2.03 ROLLER SHADES A. MOUNTING
  1. Roller shade brackets shall allow for symmetrical light gaps as small as _“ on each side of shade.
  2. System shall have a roller shade leveling adjustment that allows level adjustment while the roller shades are mounted to the brackets.
B. SHADE TUBE
  1. 2.5" aluminium extrusion
  2. Fabric shall be connected to the tube with double-sided adhesive strip applied for exact and firm mounting of the fabric and for easy adjustment of fabric to prevent telescoping.
  3. A minimum of one turn of fabric will be placed on the roller before the working section of fabric starts, to protect the fabric and smooth out the starting seam.
C. FABRICS
  1. QUALIFICATIONS

a. Fire - Provide shade fabrics tested in accordance with:

i. 1989 NFPA 701 small scale Vertical Burn Test and rated "PASS."

ii. 1996 NFPA 701 small scale Vertical Burn (telephone booth test) and rated "PASS."

D. HEM BAR
  1. Standard Sealed Hem Bar shall be a 1" wide by .1875" thick extruded aluminum bar enclosed on all sides in a thermally sealed pocket across the bottom of the shading fabric.
2.04 CONTROLS A. WALL MOUNTED CONTROLS
  1. Keypad(s) shall be able to electronically set and reconfigure shade open and close limits, shade preset positions, system groups, and system subgroups at the control without rewiring and without access to the Electronic Drive Unit.
  2. Location, quantity and function of controls to be determined by job requirements
2.05 TRANSFORMERS
All transformers shall be UL Listed
A. POWER PANEL

Panels shall accept 120VAC hardwired connections and provide centralized, power and communication landing terminals for up to 10 Electronic Drive Units.

B. J-BOX MOUNTED TRANSFORMER

Transformer shall accept 120VAC hardwired connections and provide power for one Electronic Drive unit

C. PLUG IN TRANSFORMER 100VA

Transformer shall provide line cord to connect directly to standard 120VAC grounded outlets

D. PLUG IN TRANSFORMER 50VA

Transformer shall provide integral 3 prong connector to mount directly to a standard 120VAC outlet

PART 3. EXECUTION 3.01 EXAMINATION

A. Refuse delivery of any damaged packaging.

B. Ensure all parts match specified bill of materials and purchase order.

3.02 INSTALLATION

A. Install shades in windows level and plumb to provide smooth operation.

B. Install in accordance with manufacturer’s product data and approved shop drawings

C. Field measurement and installation shall be performed by a factory-trained technician.

D. Adjust fabric on tube to prevent telescoping of fabric over time.

3.03 CLEANING

A. Touch up damaged finishes and repair minor damage in order to eliminate evidence of repair. Remove and replace work that cannot be satisfactorily repaired.

B. Clean exposed surfaces, including metal and shade fabric, using non-abrasive materials and methods recommended by the Shade Fabric Manufacturer. Remove and replace work that cannot be satisfactorily cleaned.

3.04 SCHEDULES
END OF SECTION